Lines Matching refs:cooling
15 and the software abstraction of cooling devices and thermal zones required to
21 - cooling-device: device used to dissipate heat either passively or actively
29 1. when passive cooling is activated (polling-delay-passive)
31 active cooling is activated.
58 zone and one sub-node containing all the zone cooling-maps.
73 checking this thermal zone while doing passive cooling. Setting
112 be taken are defined in another node called cooling-maps.
131 millicelsius. Any cooling action initiated by the framework is
135 cooling action is removed.
140 - active # enable active cooling e.g. fans
141 - passive # enable passive cooling e.g. throttling cpu
162 help in cooling e.g. fans can be sped up or slowed down
172 cooling-maps:
178 trip and the target cooling device state.
190 cooling-device:
193 A list of cooling device phandles along with the minimum
194 and maximum cooling state specifiers for each cooling
196 cooling-device phandle limit specifier lets the framework
197 use the minimum and maximum cooling state for that cooling
203 The cooling contribution to the thermal zone of the referred
204 cooling device at the referred trip point. The contribution is
205 a ratio of the sum of all cooling contributions within a
210 - cooling-device
287 cooling-maps {
291 cooling-device = <&CPU0 3 3>, <&CPU1 3 3>,
298 cooling-device = <&CPU0 5 5>, <&CPU1 5 5>,